Circuit breaker In = 16 A "C" 6kA
Thosetechnical
characteristics:
In:
16A
TOseries
:
MC ...
A / MCS
DIN VDE 0641 part 11 / 8-92, EN 60 898, IEC 898
Number of poles: 2
Tripping
characteristic: C
Rated
voltage Un 230/400 V ~
Maximum
calculated
operating voltage:
Variable: 230/400 V ~
Continuous: 60 V -
Minimum
rated operating voltage
Variable: 12 V ~
Continuous: 12 V -
Rated
breaking capacity In 6000 A
Energy
limitation class: 3 (according to VDE up to 32 A)
Design
frequency: 50/60 Hz
Connection:
Input: ready-to-connect Bi-Connect terminal
with
standby position
➞
1 to 25 mm2
Exit: recessed terminal ➞ 1 to 25 mm2
Login: quick connector (QuickConnect) ➞
63 A phase bus
Exit: quick connector (QuickConnect) - massive ➞
1.5 - 4 mm2
Service life of the device at rated load: ≤ 32 A 20,000 starts
> 32 A 10,000 inclusions
Protection type: IP 2x, integrated in distributor IP 30
Ambient temperature:
Workingi
temperature: -
25o to + 60o
Storage temperature: - 25° to + 80°
● Purpose: to protect cables and conductors against overload and short circuit currents.
● Mounting: DIN rail according to the electrical distribution switchboards.
● Design: modular devices.
● Switching capacity: 6 kA.
● Tripping characteristic: C.
● Number of Poles: 2
● Rated current: 16A.
● Operating voltage: 230/400V AC.
● Additional Options: Auxiliary switch (can be installed separately).